1

.3.1 Terminal connection diagram

FR-S540-0.4K to 3.7K-EC(R)

Power factor improving
DC reactor
(FR-BEL: Option)

Frequency setting signals (Analog)

10 (+5V)

2

2

3

1

4 to 20mADC (+)

4 (4 to 20mADC)

Frequency
setting
potentiometer
1/2W1k
(*3)

SE

Running

Jumper: Remove this
jumper when FR-BEL
is connected.

Motor

IM

Earth
(Ground)

Alarm
output

U

V

W

P1

Selected

Operation status
output

5 (Common)

Open collector
output common

Current input (-)

Open
collector
outputs

SINK

SOURCE

Inverter

Main circuit terminal

Control circuit input terminal

Control circuit output terminal

DC 0 to 5V
DC 0 to 10V

(*2)

When using the current input as
the frequency setting signal, set
"4" in any of Pr. 60 to Pr. 63 (input
terminal function selection), assign
AU (current input selection) to any
of terminals RH, RM, RL and STR,
and turn on the AU signal.

Earth (Ground)

RS-485 Connector (*1)

AM

5

(+)

(-)

Analog signal
output
(0 to 5VDC)

B

C

A

*5

*5

*5

RUN

*5

Take care not to short
terminals PC-SD.

PC

External transistor common

24VDC power supply

Contact input common (sink)

STF

SD

Forward rotation start

Reverse rotation start

Middle

High

Low

Multi-speed selection

Contact input common

STR *4

RH

*4

RM

*4

RL

*4

Control input signals
(No voltage input allowed)

3-phase AC
power supply

NFB

L

1

MC

L

2

L

3

REMARKS

*1 Only the type with RS-485 communication function.
*2 You can switch between the sink and source logic positions. Refer to page 25.
*3 When the setting potentiometer is used frequently, use a 2W 1k

potentiometer.

*4 The terminal functions change with input terminal function selection (Pr. 60 to

Pr. 63). (Refer to page 38, 88) (RES, RL, RM, RH, RT, AU, STOP, MRS, OH,
REX, JOG, X14, X16, (STR) signal selection)

*5 The terminal functions change with output terminal function selection (Pr. 64,

Pr. 65). (Refer to page 90) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL,
LF, ABC signal selection)