.5.9 Regarding power harmonics

The inverter may generate power harmonics from its converter circuit to affect the
power generator, power capacitor etc. Power harmonics are different from noise and
leakage currents in source, frequency band and transmission path. Take the following
counter measure suppression techniques.

The following table indicates differences between harmonics and noise:

Item

Harmonics

Noise

Frequency

Normally 40th to 50th degrees or
less (up to 3kHz or less)

High frequency (several 10kHz
to MHz order)

Environment

To-electric channel, power
impedance

To-space, distance, wiring path

Quantitative
understanding

Theoretical calculation possible

Random occurrence, quantitative
grasping difficult

Generated amount

Nearly proportional to load
capacity

Change with current variation
ratio (larger as switching speed
increases)

Affected equipment
immunity

Specified in standard per
equipment

Different depending on maker's
equipment specifications

Suppression example

Provide reactor.

Increase distance.

Suppression technique

Harmonic currents produced
on the power supply side by
the inverter change with such
conditions as whether there
are wiring impedances and a
power factor improving
reactor and the magnitudes of
output frequency and output
current on the load side.

Inv

e

rt

er

NFB

Power factor

improving AC reactor

Do not provide power factor
improving capacitor.

Power factor

improving DC reactor

Motor

IM

For the output frequency and output current, we understand that they should be
calculated in the conditions under the rated load at the maximum operating frequency.

CAUTION

The power factor improving capacitor and surge suppressor on the inverter output
side may be overheated or damaged by the harmonic components of the inverter
output. Also, since an excessive current flows in the inverter to activate overcurrent
protection, do not provide a capacitor and surge suppressor on the inverter output
side when the motor is driven by the inverter. To improve the power factor, insert a
power factor improving reactor in the inverter's primary side or DC circuit. For full
information, refer to page 18.

1

.5.10 Japanese power harmonic suppression guideline

Harmonic currents flow from the inverter to a power receiving point via a power
transformer. The harmonic suppression guideline was established to protect other
consumers from these outgoing harmonics.
1) [Harmonic suppression guideline for household appliances and general-purpose

products]
The "harmonic suppression guideline for household appliances and general-purpose
products" issued by ex-Ministry of International Trade and Industry (present Ministry
of Economy, Trade and Industry) in September, 1994 applies to the FR-S500 series
other than the three-phase 400V class. By installing the FR-BEL or FR-BAL power
factor improving reactor, this product complies with the "harmonic suppression
techniques for transistorized inverters (input current 20A or less)" established by the
Japan Electrical Manufacturers' Association.