6 how to use the control circuit terminals, 1 terminal block layout, 2 wiring instructions – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 33

Advertising
background image

24

1

.6 How to Use the Control Circuit Terminals

1

.6.1 Terminal block layout

In the control circuit of the inverter, the terminals are arranged as shown below:

Terminal screw size: M2

10

2

5

4

RL

RM RH

FM

Terminal arrangement

of control circuit

<AM>

Japanese version
NA, EC version

Terminal screw

size: M3

A

RUN

STR

PC

SE

SD

SD STF

B

C

REMARKS

For the cable size, wiring length, etc., refer to the instruction manual (basic).

1

.6.2 Wiring instructions

1) Terminals SD, SE and 5 are common to the I/O signals. These common terminals

must not be earthed.

2) Use shielded or twisted cables for connection to the control circuit terminals and run

them away from the main and power circuits (including the 200V relay sequence
circuit).

3) The input signals to the control circuit are micro currents. When contacts are

required, use two or more parallel micro signal contacts or a twin contact to prevent
a contact fault.

*Information on bar terminals
Introduced products (as of June, 2000): Phoenix Contact Co.,Ltd.

Terminal Screw Size

Bar Terminal Model

(With Insulation

Sleeve)

Bar Terminal Model

(Without Insulation

Sleeve)

Wire Size (mm

2

)

Al 0.5-6WH

A 0.5-6

0.3 to 0.5

M3 (A, B, C terminals)

Al 0.75-6GY

A 0.75-6

0.5 to 0.75

M2

(Other than the above)

Al 0.5-6WH

A 0.5-6

0.3 to 0.5

Bar terminal crimping terminal: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)

CAUTION

When using the bar terminal (without insulation sleeve), use care so that the
twisted wires do not come out.