3 current input selection "au signal": setting "4 – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 47

Advertising
background image

38

1

.8 How to Use the Input Signals (Assigned Terminals

RL, RM, RH, STR)

Pr. 60 "RL terminal function selection"
Pr. 61 "RM terminal function selection"
Pr. 62 "RH terminal function selection"

These terminals can be
changed in function by setting
Pr. 60 to Pr. 63.

Pr. 63 "STR terminal function selection"

Page 88

1

.8.1 Multi-speed setting (RL, RM, RH, REX signals): Setting "0, 1, 2, 8"

Remote setting (RL, RM, RH signals): Setting "0, 1, 2"

By entering frequency commands into the RL, RM, RH and REX signals and turning
on/off the corresponding signals, you can perform multi-speed operation (15
speeds). (For details, refer to page 32.)
If the operation panel is away from the control box, you can perform continuous
variable-speed operation with signal contacts, without using analog signals. (For
details, refer to page 86.)

1

.8.2 Second function selection (RT signal): Setting "3"

Pr. 44 "second acceleration/deceleration time"
Pr. 45 "second deceleration time"
Pr. 46 "second torque boost"
Pr. 47 "second V/F (base frequency)"
To set any of the above functions, turn on this
"RT signal".

STF (STR)

RT

SD

Inverter

Start

Second acceleration

/deceleration

1

.8.3 Current input selection "AU signal": Setting "4"

When a fan, pump etc. is
used to perform operation of
constant- pressure/
temperature control,
automatic operation can be
performed by entering the 4-
20mADC output signal of a
regulator into across
terminals 4-5.

OFF

Automatic/manual
signal switching

Manual operation

Frequency setting

potentiometer

Automatic signal

DC4-20mA

AU

SD

10

2

5

4

Across
AU-SD

Inverter

ON

Operation

Automatic

operation

4 to 20mA

Manual

operation

0 to 5V

(0 to 10V)

When the 4-20mADC signal is used to perform operation, always short the AU signal.

REMARKS

The current input is ignored if the multi-speed signal is input.

1

.8.4 Start self-holding selection (STOP signal): Setting "5"

This connection example is used when
you want to self-hold the start signal
(forward rotation, reverse rotation).
* Connected to the STOP signal to

avoid forward or reverse rotation if
forward or reverse rotation and stop
are turned on simultaneously.

STF

STR

Stop

Forward

rotation
Reverse

rotation

(Wiring example for sink logic)

SD

STOP

*