5 acceleration/deceleration time – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 71

Advertising
background image

62

CAUTION

1. The multi-speed settings override the main speeds (across terminals 2-5, 4-5, setting dial).

When the multi-speed settings and setting dial are used in the combined operation mode
(Pr. 79=3), the multi-speed settings have precedence.

2. The multi-speeds can also be set in the PU or external operation mode.
3. For 3-speed setting, if two or three speeds are simultaneously selected, priority is given to

the frequency setting of the lower signal.

4. Pr. 24 to Pr. 27 and Pr. 80 to Pr. 87 settings have no priority between them.
5. The parameter values can be changed during operation.
6. When using this function with the jog signal, the jog signal has precedence.

REMARKS

* When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions

may be affected. Check the functions of the corresponding terminals before
making setting.

The frequency-set external terminals have the following priority:
Jog > multi-speed operation > AU (terminal 4) > terminal 2

Related parameters

Maximum, minimum frequency setting

Pr. 1 "maximum frequency", Pr. 2 "minimum

frequency" (refer to page 59)

Assignment of signals RH, RM, RL, REX to terminals

Pr. 60 to Pr. 63 (input terminal

function selection) (refer to page 88)

External operation mode setting

Pr. 79 "operation mode selection" (refer to page 98)

Computer link mode

Pr. 79 "operation mode selection" (refer to page 98), communication

parameter n10 "link start mode selection" (refer to page 131)

Speed command write

Communication parameter n9 "speed command write"

(refer to page 130)

2

.3.5

Acceleration/deceleration time

Used to set motor acceleration/
deceleration time.
Set a larger value for a slower speed
increase/decrease or a smaller value
for a faster speed
increase/decrease.

Running
frequency

Acceleration

time

Deceleration

time

Time

Pr.20

Out

put

f

requ

enc

y

(Hz

)

Pr.7
Pr.44

Pr.8
Pr.45

Acceleration

Deceleration

Constant speed

Parameter

Name

Factory

Setting

<EC version>

Setting

Range

Remarks

7

Acceleration time

5s

0 to 999s



8

Deceleration time

5s

0 to 999s



20

Acceleration/
deceleration reference
frequency

60Hz

<50Hz>

1 to 120Hz

Setting is enabled when
Pr. 30 = "1".

44

Second acceleration/
deceleration time

5s

0 to 999s

Setting is enabled when
Pr. 30 = "1".

45

Second deceleration
time

- - -

0 to 999s,

- - -

- - -:
acceleration time =
deceleration time.

Setting is
enabled when
Pr. 30 = "1".

Advertising