MITSUBISHI ELECTRIC FR-S520 User Manual

Page 83

Advertising
background image

74

2

.3.18

Biases and gains of the frequency setting voltage (current)

to

You can set the magnitude (slope) of the output frequency as desired in relation
to the external frequency setting signal (0 to 5V, 0 to 10V or 4 to 20mA DC).
The "bias" and "gain" functions are used to adjust the relationship between the
input signal entered from outside the inverter to set the output frequency, e.g. 0
to 5VDC, 0 to 10VDC or 4 to 20mADC, and the output frequency.

Frequency setting voltage signal

Factory setting

0Hz( )

C2

5V or 10V

(100% C4 )

0V

Pr.73

Ou

tput

fr

e

quency

(

H

z)

( Pr.38 )

60Hz<50Hz>

Frequency setting current signal

20mA

4mA

Factory setting

( Pr.39 )

60Hz<50Hz>

Ou

tput

fr

e

quency

(

H

z)

0Hz( )

C5

(0% C3 )

(Across
terminals
2-5)

(20% C6 )

(100% C7 )

(Across
terminals
4-5)

Parameter

Name

Factory Setting

<EC version>

Setting

Range

Remarks

38

Frequency setting voltage gain
frequency

60Hz

<50Hz>

1 to 120Hz

39

Frequency setting current gain
frequency

60Hz

<50Hz>

1 to 120Hz

C2 (902)

Frequency setting voltage bias
frequency

0Hz

0 to 60Hz

C3 (902) Frequency setting voltage bias

0% *

0 to 300%

C4 (903) Frequency setting voltage gain

96% *

0 to 300%

C5 (904)

Frequency setting current bias
frequency

0Hz

0 to 60Hz

C6 (904) Frequency setting current bias

20% *

0 to 300%

C7 (905) Frequency setting current gain

100% *

0 to 300%

Setting is enabled
when Pr. 30 = "1".

* Settings may differ because of calibration parameters.
The parameter numbers within parentheses are those for use of the parameter unit (FR-PU04).
When the parameter unit (FR-PU04) is used, operation from the operation panel is not accepted.

POINT

Bias setting for 0-5VDC (0-10VDC) input

Use calibration parameters C2, C3 for setting.

Gain setting for 0-5VDC (0-10VDC) input

Use Pr. 38, calibration parameter C4 for
setting.

Bias setting for 4-20mADC input

Use calibration parameters C5, C6 for
setting.

Gain setting for 4-20mADC input

Use Pr. 39, calibration parameter C7 for
setting.

(For 4 to 20mADC input, set "4" in any of Pr. 60 to Pr. 63 (input terminal function
selection) and assign AU (current input selection) to any of terminals RH, RM, RL
and STR, and turn on the AU signal.)