2 output frequency detection [p42] [p43, 2 output frequency detection, Setting – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 88

Advertising
background image

79

2

2

.4.2

Output frequency detection

The output frequency detection
signal (FU) is output when the
output frequency reaches or
exceeds the setting. This function
can be used for electromagnetic
brake operation, open signal, etc.
You can also set the detection of
the frequency used exclusively for
reverse rotation.

Forward

rotation

Reverse

rotation

Time

Output

signal

FU

Out

p

u

t

fr

equ

enc

y (Hz

)

Pr.42

Pr.43

ON

ON

OFF

OFF

OFF

This function is effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation (fall) during vertical
lift operation, etc.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

42

Output frequency
detection

6Hz

0 to 120Hz



43

Output frequency
detection for reverse
rotation

- - -

0 to 120Hz,

- - -

- - -: Same as

Pr. 42 setting

Setting is
enabled
when Pr. 30
= "1".

<Setting>

Refer to the above chart and set the corresponding parameters.

When Pr. 43 "output frequency detection for reverse rotation"

"- - -", the Pr.42

setting applies to forward rotation and the Pr.43 setting applies to reverse rotation.
Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used
for FU signal output.

CAUTION

Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions.
Make setting after confirming the function of each terminal.

Related parameters

Assignment of FU signal to terminal

Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C

terminal function selection" (refer to page 90)

,

Refer to

,

(page 62).

Refer to

(page 58).

Refer to

(page 59).