.5 Current Detection Function Parameters

2

.5.1

Output current detection functions

If the output remains higher than the
Pr. 48 setting during inverter operation
for longer than the time set in Pr. 49,
the output current detection signal
(Y12) is output from the inverter's
open collector output terminal.

Out

put

c

u

rr

e

n

t

Time

Output current
detection
signal (Y12)

100ms

Pr.48

Pr.49

OFF

OFF

ON

Parameter

Name

Factory

Setting

Setting

Range

Remarks

48

Output current detection
level

150%

0 to 200%

49

Output current detection
signal delay time

0s

0 to 10s

Setting is enabled when
Pr. 30 = "1"

<Setting>

Parameter

Number

Description

48

Set the output current detection level.
100% is the rated inverter current.

49

Set the output current detection time. Set the time from when the output
current has risen above the Pr. 48 setting until the output current detection
signal (Y12) is output.

CAUTION

Once turned on because the current has risen above the preset detection level,

the output current detection signal is held on for at least 100ms (approximately).

Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other

functions. Make setting after confirming the function of each terminal.

Related parameters

Assignment of Y12 signal to terminal

Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C

terminal function selection" (refer to page 90)