82

2

.6 Display Function Parameters

2

.6.1

Monitor display

You can choose the display of the operation panel "monitor/frequency setting
screen".

For the Pr. 54 function, the Japanese version has the FM terminal feature, and

the NA and EC versions have the AM terminal feature.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

52

Operation panel
display data
selection

0

0, 1,

100

54

FM (AM) terminal
function selection

0

0, 1

Setting is enabled when Pr. 30 = "1"

POINT

You can also use the

SET

key to change the display. (Refer to the instruction

manual (basic) for the operation procedure.)
The pulse train output terminal FM (analog voltage output terminal AM) is
available for signal output. (Make selection using the Pr. 54 "FM (AM) terminal
function selection" value.)

<Setting>

Parameter Setting

Pr. 52

Pr. 54

Signal Type

Unit

Operation panel

LED

FM (AM)

terminal

Full-Scale Value of FM

(AM) Level Meter

Output
frequency

Hz

0/100

0

Pr. 55 "frequency monitoring
reference"

Output current

A

1

1

Pr. 56 "current monitoring
reference"

When "100" is set in Pr. 52, the monitor value changes depending on whether the
inverter is during stop or running.

Pr. 52

0

100

During running/stop

During stop

During running

Output frequency

Output frequency

Set frequency

Output frequency

REMARKS

During an error, its definition appears.

During reset, the values displayed are the same as during a stop.

For selection of the parameter unit (FR-PU04) monitor display, refer to the

communication parameter n16 "PU main display screen data selection". (Page 134)

CAUTION

The unit displayed on the operation panel is only A and other units are not displayed.

Related parameters

Speed display

Pr. 37 "speed display" (refer to page 73)

Adjustment of FM (AM) level meter full-scale value

Calibration parameter C1 "FM (AM)

terminal calibration" (refer to page 111)

Monitoring reference

Pr. 55 "frequency monitoring reference", Pr. 56 "current monitoring

reference" (refer to page 84)