9 terminal function selection parameters, Caution, 1 input terminal function selection – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 97

Advertising
background image

88

CAUTION

The frequency can be varied by RH (acceleration) and RM (deceleration)

between 0 and the maximum frequency (Pr. 1 setting).

When the acceleration or deceleration signal switches on, the set frequency

varies according to the slope set in Pr. 44 "second acceleration/deceleration time"
or Pr. 45 "second deceleration time". The output frequency acceleration and
deceleration times are as set in Pr. 7 "acceleration time" and Pr. 8 "deceleration
time", respectively. Therefore, the longer preset times are used to vary the actual
output frequency.

If the start signal (STF or STR) is off, turning on the acceleration (RH) or

deceleration (RM) signal varies the preset frequency.

CAUTION

When selecting this function, re-set the maximum frequency according to the

machine.

Related parameters

Maximum frequency setting

Pr. 1 "maximum frequency" (refer to page 59)

Output frequency acceleration/deceleration time

Pr. 7 "acceleration time",

Pr. 8 "deceleration time" (refer to page 62)

Time setting for acceleration/deceleration

Pr. 44 "second acceleration/deceleration time",

Pr. 45 "second deceleration time"
(refer to page 62)

2

.9 Terminal Function Selection Parameters

2

.9.1

Input terminal function selection

Use these parameters to select/change the input terminal functions.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

60

RL terminal
function
selection

0

61

RM terminal
function
selection

1

62

RH terminal
function
selection

2

0 to 10,

14, 16

63

STR terminal
function
selection

- - -

0 to 10,

14, 16,

- - -

Setting is enabled when Pr. 30 = "1"