2 output terminal function selection [p64] [p65, 2 output terminal function selection, Setting – MITSUBISHI ELECTRIC FR-S520 User Manual

Page 99

Advertising
background image

90

2

.9.2

Output terminal function selection

You can change the functions of the open collector and contact output terminals.

Parameter

Name

Factory

Setting

Setting

Range

Remarks

64

RUN terminal
function
selection

0

65

A, B, C
terminal
function
selection

99

0, 1, 3, 4,

11 to 16,

98, 99

Setting is enabled when Pr. 30 = "1"

<Setting>

Setting

Signal

Name

Function

Operation

Parameters

Referred to

0

RUN

Inverter running

Output during operation when the
inverter output frequency rises to or
above the starting frequency.

Pr. 2, Pr.13

1

SU

Up to frequency

Output when the output frequency is
reached.

Pr. 41

3

OL

Overload alarm

Output while stall prevention function
is activated.

Pr. 21, Pr. 22,
Pr. 23, Pr. 28

4

FU

Output frequency
detection

Output when the output frequency
rises to or above the setting.

Pr. 42, Pr. 43

11

RY

Inverter operation
ready

Output when the inverter is ready to
be started by switching the start
signal on.

12

Y12

Output current
detection

Output when the output current rises
to or above the setting.

Pr. 48, Pr. 49

13

Y13

Zero current
detection

Output when the output current
reaches 0.

Pr. 50, Pr. 51

14

FDN

PID lower limit

15

FUP

PID upper limit

16

RL

PID forward-reverse
rotation output

Outputs the detection signal under
PID control.

Pr. 88 to Pr. 94

98

LF

Minor fault output

Output when a minor fault (fan failure
or communication error warning)
occurs.

Pr. 76, Pr. n5

99

ABC

Alarm output

Output when the inverter's protective
function is activated to stop the output
(major fault).

REMARKS

The same function may be set to more than one terminal.