Troubleshooting, Prosec t2n – Toshiba T2N User Manual

Page 103

Advertising
background image

88

PROSEC

T2N

6.Troubleshooting

Error Message and Associated Information

CPU LED Display

Classification

Error Message

Information 1

Information 2

Information 3.

Related Special

Relays

RUN

FLT

Meaning of Error and Countermeasures

LP function error

Error code

Error data

S0004
S0015

A fault has been detected in the language
processor for (LP).
When the state does not change even on
starting up again, replace the CPU module.

LP execution timeout

S0004
S0015

The operation of the language processor
(LP) is not completed within the specified
time. When the state does not change even
on starting up again, replace the CPU
module.

Processing

Scan time over

Scan time

S0006
S0031

The scan time exceeds 200ms. Shorten the
scan time or use the “WDT” instruction

No END /IRET error

Program type -
Block No.

Address in block

S0006
S0030

No "END" instruction has been programmed
in the main program or the sub program, or
no "IRET" instruction as been programmed
in the interrupt program.
Insert the "END", or the "IRET" instruction.

Pair inst error

Program type -
Block No.

Address in block

S0006
S0030

There is a fault in the method of using
instruction combinations MCS/R and JCS/R.
Check that the MCS/R and JCS/R command
combinations are correct.

Operand

Program type-
Block No.

Address in block

S0006
S0030

There is a fault in the operand assignment
for the Coil instruction or the FUN
instruction. Check whether an input (X) is
allocated to an output operand.

Program

Invalid program

Program type -
Block No.

S0006
S0030

A fault has been detected in the program
control information.
After executing Memory Clear, reload the
program.

Advertising