Item

RO62

(EX10*MRO62)

Load voltage

24Vdc, +20%(MAX)/240Vac, +10%(MAX)

Maximum load

2A/point (resistive load), 1A/point (inductive load)

Minimum load

50mW (5V or more)

Number of output points

8 points (each point isolated)

ON Delay

10msec or less

OFF Delay

15msec or less

Leakage current When OFF 0mA

Voltage insulation

1500Vac / 1 minute

Current consumption

40mA (5Vdc) or less

External Relay Coil Power

Required

24Vdc +/- 10% - 100mA/all points ON

(10mA/point)

Weight

Approx 250g

1. ON/OFF life of relays:

Electrical 100,000 times

Mechanical 20 million time

2. No overload protection fuses are built into this module. Therefore

connect fuses externally suitable to the current capacity.