2.INTERNAL OPERATIONS

User’s manual

105

Initial load

When RUN start up is taking place, with RUN position (the operation mode

switch) and the ROM/RAM switch (Dip SW.2) on the front of the CPU

module is OFF (ROM), the T2N will transfer the contents of the user

program and the first 2K words of the data register (D0000 to D2047) from

peripheral memory (EEPROM) to the main memory (RAM).

The initial load is not performed if the user program is written in the

EEPROM but the contents thereof are destroyed (BCC error detection).

The T2N goes to ERROR mode.

User data initialization

User data initialization takes place after transfer from HALT mode to RUN

mode.

Refer to 2.2 System initialization for details of initialization.

ƒ

I/O mounting check

The I/O module mounting is checked basing on the I/O allocation

information.

Refer to 5.RAS functions for details.

User program check

A BCC check is performed on the user program in the main memory

(RAM).

Refer to 5.RAS functions for details.

Scan mode set up

Setting of the scan mode (floating scan or constant scan) is performed.

The scan mode is explained in 2.4.1.