Troubleshooting 84 – Toshiba T2N User Manual

Page 99

Advertising
background image

6.Troubleshooting

84

PROSEC T2N

When “Receive Time Out” is displayed in Step (4) above, communication

between the programmer and the T2N system has not been established. When

the FLT LED on the CPU module is blinking, there is a malfunction in the CPU

module. When this state does not change even if the power supply of the T2N

system is switched ON again, replace the CPU module. When “Receive Time

Out” is displayed in states without FLT blinking, check the Connection method

of the setup options of the programmer (T-PDS) and the connection state of the

connector cable. When there is no problem with the environmental setting or

the connector cable, a malfunction of communication circuit in the T2N system

or the programmer is suspected.

When the Event History has been displayed, check the registered error

message (“Event”) (No.1 is the latest registered details).

On the next and following pages, the error messages and associated

information registered in the Event History, related special relays, LED display

states after the event and their meaning are collated. When an error occurs,

check its cause and take the necessary steps.

In the “Error Down” state, operations such as program correction will not be

possible. Therefore, carry out operations such as correction after executing

“Error Reset” from the programmer. In order to start up RUN again, either shift

the operation mode switch to RUN after first shifting it to HALT, or execute the

Operation command from the programmer.

In the Table on the next and following pages, the meanings of the symbols for

the system LED displays are as follows:-

:Lit

:Out

:Blinking

:No effect on state.

If RUN is started in the state in which the ROM/RAM shift switch has been

set to ROM (other than when the operation mode switch is P-RUN), the

contents of the EEPROM will be transferred to the RAM memory, and any

corrected contents of the RAM memory will be erased. Therefore, when

setting to RUN after correcting the program in order to check its operation,

start up RUN after executing “program write” by a T-PDS Memory

Management menu.

NOTE