1.System Configuration

18

PROSEC T2N

Type

Description

Specification

AO31

Analog output
(8bit)

2-channel (not isolated between channels),
1-5V/0-10V/4-20mA, 8bit resolution

AO22

4-channel (not isolated between channels),
4-20mA /1-5V,12bit resolution

AO32

Analog output
(12bit)

4-channel (not isolated between channels),
-10V - +10V,12bit resolution

PI21

Pulse input

1-channel (two phase, with zero marker),
5/12Vdc, 100kpps (max), 24bit counter

MC11

Single-axis
positioning

1 axis, 100kpps(max.), position data memory
capacity 64 points

CF211

Serial Interface

RS-232C 1port,
Common memory 160W

×

2

1.8

Data Transmission

By applying the following 4 types of data transmission module according to the

Module

system requirements, the T2N can configure the flexible and efficient control

systems.

TOSLINE-F10

PLC to PLC data linkage and remote I/O systems are configured by the
TOSLINE-F10 data transmission equipment.

Up to 8 T2 stations can be mounted in any slots, in the same way as I/O modules.

MS211/RS211

(High-speed setting)

MS211/RS211

(Long-distance setting)

Topology

Bus (twisted-pair cable)

Transmission speed

750kbps

250kbps

Transmission Distance

500m

1km

Number of stations

max. 32stations

Transmission capacity

32 words (L/LW)

Response speed

7ms(when 32 words)

12ms(when 32 words)

For detailed specifications of each I/O module, see Section 2.3 I/O Module