5. Programming Language

(A) HTOA (n) (B)

(A) ATOH (n) (B)

(A) ABS (B)

(A) +1· (A) DABS (B) +1· (B)

(A) NEG (B)

(A) +1· (A) DNEG (B) +1· (B)

(A) DW (B) +1· (B)

(A) 7 SEG (B)

(A) ASC (B)

(A) BIN (B)

(A) +1· (A) DBIN (B) +1· (B)

(A) BCD (B)

(A) +1·(A) DBCD (B) +1· (B)

(A) +1· (A) FLT (B) +1· (B)

(A) +1· (A) FIX (B) +1· (B)

Ladder Diagram Instructions (Function Instructions)

Group

FUN

No.

Name

Representation

Summary

Number of

steps

required

Execution

time

required

(

µ

s)

Remarks

Conversion

62

HEX-ASCII conversion

Converts the HEX data in n registers headed by (A)
into ASCII data and stores them in the registers
headed by (B).

4

160+75.5n

63

ASCII-HEX conversion

Converts the ASCII data in n registers headed by (A)
into HEX data and stores them in the registers
headed by (B).

4

143+39.4n

180

Absolute value

Stores the absolute value of (A) in (B).

3~4

70

181

Double-length absolute
value

Stores the absolute value of (A)+1 and (A) in
(B)+1•(B).

3~5

103

182

2's complement

Stores the 2's complement of (A) in (B).

3~4

68

183

Double-length 2's
complement

Stores the 2's complement of (A)+1•(A) in
(A)+1• (B).

3~5

103

184

Double lenght conversion

Converts the signed data in (A) into double-length
data, and stores in (B)+1•(B).

3~4

85

185

7-segment decode

Converts the bottom 4 bits of (A) into 7-segment
code, and code stores in (B).

3~4

73

186

ASCII conversion

Takes the alphanumerics (maximum 16 characters)
indicated by (A) and converts them into ASCII code.
Stores the result in the location headed by (B).

3~10

262

188

Binary conversion

Converts the BCD data in (A) into binary data and
stores it in (B).

3~4

105

189

Double-length binary
conversion

Converts the double-length BCD data in (A)+1•(A)
into binary data and stores it in (B)+1•(B).

3~5

175

190

BCD conversion

Converts the binary data in (A) into BCD data and
stores in in (B).

3~4

101

191

Double-length BCD
conversion

Converts the binary data in (A)+1•(A) into BCD data
and stores it in (B)+1•B).

3~5

169

204

Floating point conversion

Converts the double-length integer of (A)+1•(A) into
floating point data and stores it in (B)+1•(B).

3~5

106

363

µ

s

(max)

205

Fixed point conversion

Converts the floating point data of (A)+1•(A) into
double-length integer data and stores it in (B)+1•(B).