Troubleshooting, Prosec t2n – Toshiba T2N User Manual

Page 105

Advertising
background image

90

PROSEC

T2N

6.Troubleshooting

Error Message and Associated Information

CPU LED Display

Classification

Error Message

Information 1

Information 2

Information 3.

Related Special

Relays

RUN

FLT

Meaning of Error and Countermeasures

SFC step No. error

Program type -
Block No.

Step No.

S0006
S0030

Is there multiple use of step Nos. in the SFC
program, or do the steps No.
designated by the initial step and the end
step not agree?. Change the step Nos. or
check the step No. of the end step.

SFC marco No. err

Program type -
Block No.

Macro No.

S0006
S0030

There is multiple use of a macro No. Or the
same macro program is called in 2 or more
places. Change the macro Nos. Or arrange
for the macro
program to be called in only 1 place.

No SFC macro entry

Program type -
Block No.

Macro No.

S0006
S0030

The macro program of the macro No.
designated by a macro step has not been
programmed. Check whether the macro
program has been programmed, or whether
the macro program No. is not in error.

SFC jump label err

Program type -
Block No.

SFC jump label
No.

S0006
S0030

There is multiple use of an SFC jump label
No.Change the SFC jump label No.

No SFC jump label

Program type -
Block No.

SFC label No.

S0006
S0030

The SFC label instruction for a jump label
No. designated by an SFC jump instruction
has not been programmed.
Program the SFC label instruction.

Duplicate SFC No.

Program type -
Block No.

SFC program No.

S0006
S0030

There is multiple use of an SFC program No.
Change the SFC program No.

Program

Invalid SFC prog

Program type -
Block No.

S0006
S0030

The initial step/end step or end, or the
macro/macro end, do not correspond. Alter
the program so that the initial step/end step
or end, or the macro/ macro end correspond.