3.Application Precautions for I/O Modules

User’s manual 57

(1) Use a shielded twisted-pair cable for the analog input signal line, and wire

over the minimum distance. Carry out the grounding of the cable shield on

the analog input side(the T2N side).(1) in the dwawing below is the basic.

Sometimes, operation is more stable if the wiring is as in (2)or(3).

(1)

(2)

(3)

Analog
input
module

Analog
input
module

Analog
input
module

(2) Sometimes the conversion values are unstable,depending on the voltage

state of the external 24Vdc power supply.

If the conversion result is not stable, make the external power supply for

analog use a dedicated power supply.

Use of the 24Vdc external supply power source of the T2N power supply

module is recommended.

(3) All intrinsically shielded cables are fitted with ferrite choke adjacent to

analog inputs/outputs, and must have ground connections to grounded

metalwork within 5cm for applying to the EMC Directive.