Programming language, Prosec t2n – Toshiba T2N User Manual

Page 241

Advertising
background image

5. Programming Language

228

PROSEC T2N

(A) TON (B)

(A) TOF (B)

(A) SS (B)

C CNT Q
E (A) (B)

MCS

MCR

MCS n

MCR n

TRG (A)

Ladder Diagram Instructions (Sequence Instructions)

Group

FUN

No.

Name

Representation

Summary

Number of

steps

required

Execution

time

required

(

µ

s)

Remarks

Sequence
instructions

ON delay timer

Turns output ON when set period specified by (A)
has elapsed since input came ON. (B) is timer
register.

2

0.44

OFF delay timer

Turns output OFF when set period specified by (A)
has elapsed since input went OFF. (B) is timer
register.

2

0.44

Single shot timer

Turns output ON only for the set period, specified by
(A), starting when input comes ON. (B) is timer
register.

2

0.44

Counter

When enable input (E) is ON, counts the number of
times the count input (C) has come ON. When count
value becomes equal to set value specifiedby (A),
turns output (Q) ON. (B) is counter register.

2

0.44

Master control set

Turns ON power rail between MCS and MCR when
MCS input is ON.

1

0.22

Master control reset

1

0.22

134

Master control set
(with nesting number

Turns on power rail to corresponding MCR when
MCS input is ON. n is a nesting number.
(1 - 7).

2

61

135

Master control reset
(with nesting number

2

58

148

Timer trigger

When input is changed from OFF to ON, clears timer
register specified by (A) and activates timer.

2

153