2.INTERNAL OPERATIONS

108

PROSEC T2N

The status of the external input signals from the input module is read onto the

I/O register/device (XW/X), the output register/device (YW/Y) status is output to

the output module. This process takes place before user program execution

and is done in batches, hence name batch I/O processing. Batch I/O

processing proceeds as follows.

Batch inputting

··· signals from the input module with no i specification on

I/O allocation and input registers/devices (XW/X) which

are not forced

Batch outputting ··· output register/device (YW/Y) corresponding to output

modules with no i specification on I/O allocation

Also, the data transmission module (TOSLINE-S20LP, TOSLINE-F10, TOSLINE-

30) and the link register relay (W/Z and LW/L) within the CPU module run the

data exchange.

2.4.2

Batch I/O processing

I/O register/device

L0F

L1F

L2F

L3F

···
···
···
···

L01

L11

L21

L31

L00

L10

L20

L30

XW000

XW001

YW002

YW003

link register/relay

W0000

W0001

W0002

W0003

link relay

input module

output module

link register allocated
to TOSLINE-S20LP/30

link relay allocated
to TOSLINE-F10

TOSLINE-S20LP/30

TOSLINE-F10

LW000

LW001

LW002

LW003