The constant scan mode has a specified time cycle for scanning. The set up

range of the cycle is 10 - 200ms (10ms units). Use this scan cycle to avoid

variation in scan intervals.

The action of the constant scan when the cycle is fixed at 50ms is shown in the

following diagram.

Scan mode selection is performed by setting up the scan cycle in the system

information menu of the programmer.

To select floating scan, do not set up a scan time (leave blank).

With the constant scan the scan time can be set up within the range 10 - 200ms

(10ms units).

Note)

In the constant scan if the time for one scan is exceeded in a specified

cycle it becomes a floating scan, and the fixed time scan retard flag

(special relay - S0008) comes ON. Also, when the scan time reverts

to within the specified cycle the scan cycle returns to the original

constant scan.

scan cycle (fixed at 50ms)

mode

I/O

timer

user program

mode

I/O

timer

user program

scan cycle (fixed at 50ms)

immediately to next can

mode

I/O

timer

mode

timer

I/O

user program

mode

user program

fixed time scan

fixed time scan

returns to constant scan