3. User Data

152

PROSEC T2N

The following Tables describe the functions and address ranges for each
function type of registers and devices.

Codes

Input registers... XW
Input devices ... X

Addresses

Input registers... 000-127 (128 words)
Input devices ... 0000-127F (2048 points)

Functions

These are allocated in the input module as register units (word units) by
performing input/output allocation. The signal state inputted to the input
module is stored in the corresponding input register by batch
input/output timing (except for modules which have the designation i
attached when allocating). An input device expresses 1 bit of the
corresponding input register.
The data of input registers/input devices basically do not change during
1 scan. However, when executing a direct I/O instruction (FUN235),
data is read from the corresponding input module when the instruction
is executed and is stored in an input register/input device (XW/X). Thus,
the data changes during the scan.

Codes

Output registers ... YW
Output devices ... Y

Addresses

Output registers ... 000-127 (128 words)
Output devices ... 0000-127F (2048 points)

Functions

These are allocated in the output module as register units (word units)
by performing input/output allocation. The data stored in the output
register is written to the corresponding output module by batch
input/output timing, and the state of the output signal of the output
module is determined (except for modules which have the designation i
attached when allocating). An output device expresses 1 bit of an
output register.

3.2

Registers and Devices

Output Registers and

Output Devices

Input Registers and

Input Devices

}

Common use as output
registers/output devices

}

Common use as output
registers/output devices

Advertising