Specification, User’s manual 37 – Toshiba T2N User Manual

Page 52

Advertising
background image

2.Specification

User’s manual 37

4-Channel Analog Input

(8-bit) (Continued)

250

200

150

100

50

0

(b) (c)

1 5

250 (a)

200

150

100

50

0

4 10

A/D Conversion

Digital Value

10(V)
Analog value

D = Digital Value

A = Analog Value

20(mA)
Analog value

(a) 4-20mA range : D = 15.625 x A-62.5
(b) 1-5V range : D = 62.5 x A-62.5
(c)

0-10V range : D = 25 x A

Data Format

F E D C B A 9 8 7 6 5 4 3 2 1 0

B * * * * * * * D D D D D D D D

XW

D : Data bit (8 bits)

0-250 (H00-HFA)

(Over-voltage/over-current input 255 counts)

B : External line abnormal detection bit

0 = Normal

1 =Abnormal

* : Always 0

When all data bits are 0

When all data bits are 1

CH4

CH3

CH2

CH1

O

F

XWn+3

XWn+2

XWn+1

XWn

4 words occupied

(X4W)

1. In the voltage input specification, when there is an open-circuit

between the input terminals, the data bits do not become 0. (They

become indeterminate between 1 and 250).

2. It is recommended that unused channels be shorted between the

input terminals.

NOTE

Digital Value

Current input line open

External power is OFF

Advertising