2 functional specifications, Overview, User’s manual – Toshiba T2N User Manual

Page 110

Advertising
background image

1.Overview

User’s manual

97

Item

Specifications

Control Method

Stored program, cyclic scan system

I/O Method

Batch I/O(refresh), Direct I/O, or combination

Number of I/O points

2,048 points / 128 words

Program
language

Ladder diagram (relay symbol + function block)
SFC (Sequential Function Chart)

Program
capacity

23.5K steps

Memory

Main memory : RAM (battery back up)
Optional memory : EEPROM

RAM memory
back-up

Built-in battery (more than 5 years/ 25

°

C)

Instructions

Basic ladder instructions:24, function block instructions:192
transfer(single length/double length/registertable)
arithmetic calculation(single length/double length/binary/BCD)
logical operation(single length/double length/binary/BCD)
comparison(single length/double length,sign/unsign)
program control(jump/FOR-NEXT/subroutine and others)
function(limit/trigonometric integral/PID/function generator
and others)
conversion(ASCII/BCD/7 segment/HEX-ASCII/ASCII-HEX
floating point math function and others)
Other functions

User

Program

Execution
speed

0.33

µ

s / contact,0.44

µ

s / coil

1.2

µ

s / transfer,1.6

µ

s / addition

Scanning system

Floating scan/constant scan (interval : 10-200ms, 10ms units)

Multitasking

1 main program, 1sub program
1 timer interrupt (5-1000ms, 5ms units), 4 I/O interrupt

I/O
device/register

2,048 points/128words (X / Y, XW / YW batch I/O)

(I / O, IW / OW direct I/O)
(1 word is 16 bit.)

Auxiliary

device/register

4,096 points / 256words (R/RW)

Special

device/register

4,096 points / 256words (S/SW)

Timer

device/register

512 points (T./T) (T000-T063 : 10ms)

(T064-T511 : 0.1sec.)

Counter

device/register

512 points (C./C)

Data register

8192 words (D)

Link

device/register

16,000 points / 2,048words (Z/W)
(for TOSLINE-S20,TOSLINE-30)

Link

relay/register

4,096 points / 256words (L/LW)
(for TOSLINE-F10)

File register

1,024words (F)

Expanded

file register

24,576words (8,192words

3banks

accessed by using XFER instruction)

Index register

I, J, K (total 3words)

User

data

Retentive
memoory

User specified for RW,T,C and D

Diagnosis

Battery level, I/O bus check, I/O respomse, I/O parity,
Watch dog timer, illegal instruction, LP check, others

Monitoring

Event history record, scantime measurment, others

RAS

Debugging

Online trace monitor, force, sampling trace, status latch, others

1.2

Functional Specifications

Use READ/WRITE instruction in order to access transmission data of
TOSLINE-S20 in the T2N.
The T2N doesn

’t support automatic data refresh of TOSLINE-S20.

NOTE