Installation and wiring 64 – Toshiba T2N User Manual

Page 79

Advertising
background image

4.Installation and Wiring

64

PROSEC T2N

(2) Isolated Installation

When the mounting frame has an unstable earth potential, or when it is not

conductive, securely mount the unit with isolation, as shown below.

Dedicated single-point ground

Basic unit

Expansion unit

Isolate from the
mounting surface

FG wiring (2mm

2

) shortest wiring

Power supply modules

(3) When there is no grounding point

When suitable grounding is not available (no dedicated grounding point),

mount by the method of (2) Isolated Installation.

There is no problem with operation if there is mutual connection between

the FG terminals of the T2N itself. However, for safety, carry out single-

point grounding via an impedance* close to the frame.

When a resistor

: Ground the frame via 1W-1

approx.

When an inductance : Ground to the frame via 2A-100

µ

H approx.

*

;