3 cpu check, 4 program check, Troubleshooting – Toshiba T2N User Manual

Page 94

Advertising
background image

6.Troubleshooting

User’s manual

79

When the “POWER” LED of the power supply module is lit, but the “RUN” LED

of the CPU module is out, check the following items.

When it blinks even if power

supply

is on, CPU module is defective.
Replace the CPU.

Is the FLT

LED blinking? Blinking

Out or lit.

Is the FLT LED lit?

An error has occurred.
Check the content of the Event
History.

Lit

Out

Is the CPU module
operation mode switch to
RUN?

Shift to RUN.

NO

YES

Is the RUN/Stand-By
switch set to OFF
(RUN)?

It starts up in the HALT

mode

despite the setting

of the

operation

mode switch.
Therefore, either

shift the

operation

mode switch

HALT

RUN or start

RUN from the programmer.

NO

Is the RUN LED
blinking?

Blinking

OFF
(RUN)

It is in the HOLD mode.
Release HOLD using the
programmer.

When the control operation does not operate properly although the program is

executed, check the following items.

(1) Is there an output to the same coil or register at 2 or more places in 1 scan,

or, is there an overlap of the device for coil instruction and function block

instruction?

(2) Is there an attempt to input a signal which changes faster than the scanning

cycle?

(3) Is the same timer register or counter register being used for multiple timer

instructions or counter instructions?

(4) When interrupt is in use, is a device or register operating during the interrupt

program which affects the operation of the main program?

(5) Is any EEPROM error occured?(S0039, S0051 is 1.)

In this case, carry out EEPROM write command by the programmer.

6.4

Program Check

6.3

CPU Check

Advertising