5.Maintenance and Checks

70

PROSEC T2N

Recommended daily checks for optimum system performance

Item

Content of Check

Countermeasure

when Abnormal

POWER(Red)

:Lit when 5V power
supply normal

RUN(Green)

:Lit when operating
normally

FLT(Red)

:Out when CPU and
I/O normal

Check the LEDs on
the front of the power
supply modules and
CPU module

BAT(Green)

:Lit when battery
voltage normal

When the state of an
LED is not normal, follow
the procedure
in 6.Trouble-shooting.

Check the LED
displays of the input
modules
(Digital input)

The corresponding LED
should be lit when an
external input signal is
ON.

Check whether the

input voltage is within
the specified value.

Check whether there is

any slack in the input
terminal block.

Check whether the

module is securely
mounted.

Check the LED
displays of the output
modules
(Digital output)

When the output is ON,
the corresponding LED
should be lit and the
corresponding external
load should operate.

Check whether the

external load voltage is
within the specified
value

Check the built-in fuse.

Check whether there is

any slack in the output
terminal block.

Check whether the

module is securely
mounted.

Check the switch
position on the CPU
module

Operation is executed
when the operation mode
switch(HALT/RUN) is to
Run.

Put the switch to
the specified position.

See Ethernet/TOSLINE-S20LP of the T2N user’s manual regarding status

display LEDs for built-in networking.