2 power supply module, System configuration 6, Prosec t2n – Toshiba T2N User Manual

Page 21

Advertising
background image

1.System Configuration

6

PROSEC T2N

1.2

Power Supply Module

Power supply modules are mounted on the left -end slots of all units. There are
two types according to the power voltage. Select one as required.

Model

Power Voltage

Output Rating

Weight

TPS261**S

100 - 240Vac
(+10%/-15%)

EX10*MPS31

24Vdc
(+20%/-15%)

Internal 5V power supply : 2.5A (max.)
External power supply : 24V,+10%/-10%
0.5A (max.)
(Internal + external total 15W or less)

Approx.
300g

External 24Vdc Output Terminals

These terminals can be used to supply 24Vdc power to external devices such as
sensors or relay output modules. 24Vdc(

±

10%)-0.5A(max.)

Run Signal Output Terminals

When the T2N is in the operating mode(RUN), built-in contact is closed.
240Vac(+10%)/24Vdc(+20%)-2A(max.)
(Can also be used on expansion units)

Power Supply Terminals

Connect to the power supply line. (See 4.7 Wiring the power supply).

Line Filter Ground Terminal / Frame Ground Terminal

These are grounding terminals. (See 4.6 Grounding methods).

RUN

1. The maximum rated output of the power supply module is 15W, this includes the

internal 5Vdc and external 24Vdc output combined. Configure the system, referring to
the Module Current Consumption Table on the next page, so that the following equation
is satisfied.
15W

5V

×

Total 5V current (max. 2.5A) + 24V

×

external 24V current (max. 0.5V)

2. Do not connect the external 24V supply terminals to the other power supply systems,

and do not run the wiring over long distances.

3. This power supply module is dedicated power supply for the T2N and T2E/T2/EX100.

Do not use it by itself for other purposes.

TOSHIBA

POWER

+

-

OUT

OUT

NC

NC

IN

24Vdc

L

N

LG

FG

Terminal block
eject levers

Power supply
terminals

Power LED

Line filter ground terminal

External 24Vdc
output terminals

Frame ground terminal

Run signal output
terminals

NOTE