56 PROSEC T2N

(1) Over-Current Protection Coordination

One 2A fuse per 4 output points is mounted in the triac output module.

Although, taking account of protecting elements by the fuse blowing even

in load short circuits, when the fuse blows the semiconductors are

subjected to considerable damage. Therefore, take care in handling and

wiring so that short circuits will not occur.

(2) Output Surge Protection

Triac

output

module

L

Surge absorption element

A suitable surge absorption element should be selected according to the

application.

1. Varistor (for voltage

clamping)

(peak) voltage

2. Snubber (CR) circuit

(for high-frequency
attenuation)

Rated voltage about 1.2 times
the maximum power supply

R : 0.5-1

per 1V coil voltage

C : 0.5-1

µ

F per 1A coil

current
(Non-polar capacitor)

(1) It is necessary to supply a +24V power supply to the internal control circuit

of the relay output module. Therefore, connect a 24Vdc + 10% power

supply between the + and - terminals.

(2) No overload protection fuse is built into the relay output module.

Therefore, always install a fuse suited to the current capacity.

12-point relay output module

Fuse

(3) Output Surge Protection

The installation of a surge absorption element for the induced load, as

described in the paragraphs on the transistor output module and the triac

output module, is recommended.

Please note that, if it is
not protected with a
fuse, the module
pattern will burn out
when there is a load
short-circuit.

NOTE

3.3

Triac Output Module

Application Precautions

3.4

Relay Output Module

Application Precautions