Ras functions, User’s manual – Toshiba T2N User Manual

Page 144

Advertising
background image

5.RAS Functions

User’s manual

131

(3) Register value validity check function

This function checks that the register value is within the specified

numerical value range. There can be up to a maximum of 4 registers, a

minimum and maximum value is registered for each. Also, it is possible to

select the register value to be taken as an integer (signed) or as a positive

integer (unsigned).

The check is carried out immediately before starting a scan, the results are

stored in the special relay S0143-S0146 (within the range: 0, outside the

range: 1).

The register and the numerical value range are registered in programmer

system diagnosis mode.

XW034

unsigned

0

400

200

XW035

signed

-1500

1500

2000

D0011

unsigned

H0200

H9000

H1234

W0100

signed

-300

600

-1000

comparison

result

registered

register

type

minimum

maximum

present register

value

register 1 (XW034) .... S0143 = 0

register 2 (XW035) .... S0144 = 1

register 3 (D0011) ..... S0145 = 0

register 4 (W0100) .... S0146 = 1