4.Installation and Wiring

62

PROSEC T2N

1. Separate the expansion cables as far as possible from other cables. In

particular, isolate them at least 200mm from power lines.

2. 4 types of expansion cables are available - 0.3m, 0.5m, 0.7m and 1.5m.

Select according to the positions of the units.

Grounding Point

It is advisable, for the grounding of electronic devices to carry out dedicated

grounding which is isolated from that of power systems, and to carry out

single-point grounding between 2 or more electronic devices. In the T2N,

noise-proofing is designed which takes the actual application into account, and

it has a satisfactory noise-immunity without carrying out grounding of the device

itself. However, as a precaution, correct grounding is recommended from the

viewpoint of reliability.

Carrying out grounding, check against the following criteria.

(1) The electronic equipment case must not become a path for a ground

current. (High-frequency currents are particularly harmful)

(2) Equalise the ground potentials when 2 or more units of electronic

equipment are to be connected. (Single-point grounding is best)

(3) Do not connect to power system earths. (High-frequency isolation is

necessary)

(4) Do not connect to unstable earths. (parts with unstable impedance such

as painted screws, and parts subject to vibration)

4.5

Grounding

NOTE