1.System Configuration

8

PROSEC T2N

1.3

CPU Module

There are three types of CPU modules with functions as shown below.

Type

Specification

PU215N

RAM(battery back-up) + EEPROM, User program 23.5k step,
ladder, SFC, real time clock, enhanced communication function

PU235N

PU215’s function + Ethernet

PU245N

PU215’s function + Ethernet + TOSLINE-S20LP

Status display LEDs : Show operation states of the T2N

Lit

Operating state (RUN Mode)

Blink

HOLD Mode

RUN
(Green)

Out

Stopped state (HALT Mode) or Error Mode

Lit

CPU abnormal

Blink

Program abnormal

FAULT
(Red)

Out

Normal

Lit

Battery normal

Blink

Battery getting abnormal

BAT
(Green)

Out

Battery abnormal or no battery

Status display LEDs : Show operation states of the Ethernet/TOSLINE-S20LP
For details of operation mode, see Ethernet/TOSLINE-S20LP user’s manual.
These all LED’s color is green.

ERUN

Operating state (Ethernet)

ET/R

Data transmission/receive state (Ethernet)

EACC

T2N’s accessing state for Ethernet

SRUN

Operating state (TOSLINE-S20LP)

SONL

Online state of TOSLINE-S20LP

SACC

T2N’s accessing state for TOSLINE-S20LP

Status display LED
(RUN, FauLT, BATtery)

Operation Mode Switch
(HALT, RUN, P-RUN)

Setting Switches of
Operation Mode

Programmer port connector
(RS232C)

Communication port connector
(RS232C/RS485)

Ethernet status display
(ERUN, ET/R, EACC)

TOSLINE-S20LP status
display
(SRUN. SONL, SACC)

Station address switches
for TOSLINE-S20LP

Communication connectors
for TOSLINE-S20LP

Communication connectors
for Ethernet