5 fuse replacement, Maintenance and checks 76 – Toshiba T2N User Manual

Page 91

Advertising
background image

5.Maintenance and Checks

76

PROSEC T2N

1.The battery should be replaced with power OFF. The time with battery

removed should be within 5 minutes. If the battery is kept removed for

a long time, the contents of the RAM memory will be erased, so

please take care.

2.When connector of the battery is disconnected, an LED (BAT) is out.

Any error message about the battery can’t be registered in the Event

History Table in this case.

3. When handling the battery, take care of the following points.

* The voltage is not compatible with manganese dry batteries and

alkali batteries. Do not use these as substitutes.

* Never let the + and - of the battery be shorted.

* Never dismantle batteries, overheat them or put them into a fire.

* Never try to charge a battery. This is not possible.

4. Do not use a battery which has been stocked more than 3 years since

manufactured date.

5.The battery is a dedicated product with lead wires and connectors

attached. Order it from Toshiba.(Product Code:EX25SER6)

The following fuses are used in the T2N modules.

These fuses are recommended minimum spares and will allow operation to be

resumed immediately in the event of any failure.

Module

Fuse Rating

Model

Quantity

PS31 Glass tube 125V-2A(normal fusion)

EX10*SFB20

1

Power

Supply PS261 Glass tube 250V-3A(normal fusion)

TFU923*AS

1

DO31 Glass tube 250V-5A(quick fusion)

EX10*SFA50

1

DO32 Glass tube 250V-2A(quick fusion)

EX10*SFA20

4

Output

AC61 Glass tube 250V-2A(normal fusion)

EX10*SFC20

3

5.5

Fuse Replacement

NOTE

Advertising