E6581090

I-3

9

9.1.3.2 The models without EMI filters

(1) Shingle-phase 100V class : VFNC1-1001P to 1007P

Three-phase 200V class

: VFNC1-2001P to 2022P

Shingle-phase 200V class : VFNC1S-2002P to 2022P

This subsection explains what measures must be taken to satisfy the EMC directive.
Insert a recommended EMI filter (Table 2) on the input side of the inverter to reduce radiation
and transmission noises. In the combinations listed in Table 2, inverters were checked for
conformity with the EMC directive. For inverters used in Japan, it is recommended to use the
NF series of noise filters.
Table 2 lists noise filters recommended for the inverters.

Table 2. Recommended EMI filter selection

Voltage class

Inverter

Filter for class A

Compliance Motor cable

length 20m or less

Filter for class B

Compliance Motor cable

length 5m or less

VFNC1-2001P

EMFA2006Z

-

VFNC1-2002P

EMFA2006Z

-

VFNC1-2004P

EMFA2006Z

-

VFNC1-2007P

EMFA2006Z

-

VFNC1-2015P

EMFA2015Z

-

Three-phase
200V class

VFNC1-2022P

EMFA2015Z

-

VFNC1S-2002P

EMFAS2011Z

-

VFNC1S-2004P

EMFAS2011Z

-

VFNC1S-2007P

EMFAS2011Z

-

VFNC1S-2015P

EMFAS2025Z

-

Single-phase
200V class

VFNC1S-2022P

EMFAS2025Z

-

VFNC1S-1001P

EMFAS2011Z

-

VFNC1S-1002P

EMFAS2011Z

-

VFNC1S-1004P

EMFAS2011Z

-

Single-phase
100V class

VFNC1S-1007P

EMFAS2025Z

-

VFNC1S-2002PL

With a built-in filter

With a built-in filter

VFNC1S-2004PL

With a built-in filter

With a built-in filter

VFNC1S-2007PL

With a built-in filter

With a built-in filter

VFNC1S-2015PL

With a built-in filter

With a built-in filter

Single-phase
200V class

Built-in filter

type)

VFNC1S-2022PL

With a built-in filter

With a built-in filter

(2) The main cables such as input to the EMI filter and output of the inverter and the signal cables

should be shielded, then cable length should be wired as short as possible. The main input
cable should be separated from the main output cable, and cables for control signal also should
be separated from main cables, not wiring parallel and not bundling, cross the wires where
necessary.

(3) Install EMI filter and inverter on the same metal back plate in an inverter panel. The metal back

plate or the cubicle must be grounded absolutely, by using short thick wires, separated from the
main cables.

(4) Please separate input cable to EMI filter from output cable as much as possible.

(5) Shielded cables should be grounded on the metal back plate in order to reduce the radiated

noise from the other cables. It is an effective measure that shielded cables are grounded close
to the inverter or/and operation panel or/and EMI filter(less than 10cm).

Strip the cable and fix it to the metal plate by means
of a metal saddle for electrical work or equivalent.

Shielded cable