E6581090

M-4

13

(Continued)

Error
code

Alarm

code

Problem

Possible causes

Remedies

G

0033

CPU
communications
error

• A communications error occurs

between control CPUs.

• Make a service call.

G

0034

Excessive torque
boosted

• The torque boost parameter

XD

is set too high.

• The impedance of the motor is

too small.

• Decrease the setting of the

torque boost parameter XD

• If no improvement results,

contact Toshiba Technical
Support Center.

 

* With a parameter, you can choose between trip-on and -off.

[Alarm information] Each message in the table is displayed to give a warning but does not cause the

inverter to trip.

Error
code

Problem

Possible causes

Remedies

QHH

ST terminal OFF

• The ST-CC circuit is opened.

• Close the ST-CC circuit.

OQHH

Undervoltage in
main circuit

• The supply voltage between R,

S and T is under voltage.

• Measure the main circuit supply

voltage.
If the voltage is at a normal
level, the inverter requires
repairing.

TVT[

Retry in process

• The inverter is in the process of

retry.

• A momentary stop occurred.

• The inverter is normal if it

restarts after several tens of
seconds.
The inverter restarts
automatically. Be careful of
the machine because it may
suddenly restart.

GTT

Frequency point
setting error

• The frequency setting signals at

points 1 and 2 are set too close
to each other.

• Set the frequency setting

signals at points 1 and 2 apart
from each other.

ENT

Clear command
acceptable

• This message is displayed

when pressing the STOP key
while an error code is
displayed.

• Press the STOP key again to

clear the trip.

GQHH

Emergency stop
command
acceptable

• The operation panel is used to

stop the operation in automatic
control or remote control mode.

• Press the STOP key for an

emergency stop.
To cancel the emergency stop,
press any other key.

JK

/NQ Setting error alarm /

An error code and
data are displayed
alternately twice
each.

• An error is found in a setting

when data is reading or writing.

• Check whether the setting is

made correctly.

JGCF
/GPF

Display of first/last
data items

• The first or last data item in the

CWJ

/CWH data group is

displayed.

• Press the MON key to exit the

data group.

FD

DC braking

• DC braking in process

• The message goes off in several

tens of seconds if no problem
occurs. Note)

G

Flowing out of
excess number of
digits

• The numeric value displayed

(e.g., frequency) has a larger
number of digits than the
display panel. (The number
next to the E refers to the
excess number of digits.)

• When a frequency is displayed,

decrease the setting of H
(free unit).

(Continued overleaf)