Description of terminals

2.3.1 Main circuit terminals

This diagram shows an example of wiring of the main circuit. Use options if necessary.

Power supply and motor connections

or

or

VF-nC1

Power
supply

E

R/L1 S/L2 T/L3

U/T1 V/T2 W/T3

Motor

Powerlines are
connected to R, S and T.

Motorlines are connected
to U, V and W.

No-fuse
breaker

Connections with peripheral equipment

Motor

Power
supply

Inverter

DC reactor

No-fuse
breaker

R/L1

S/L2

T/L3

PC/- PA/+

PO

/T2

/T1

/T3

IM

Magnetic
contactor

Input

reactor

Noise reduction

filter

Zero-phase
reactor

Main circuit

Terminal symbol

Terminal function

Grounding terminal for connecting inverter case. 2 grounding terminals.

R/L1, S/L2,
T/L3

100V class: 1-phase 100V to 115V - 50/60Hz
200V class: 1-phase 200V to 240V - 50/60Hz, 3-phase 200V-240V - 50/60Hz
*1-phase series have R/L1 and S/L2 terminal.

U/T1, V/T2,
W/T3

Connect to a (3-phase induction) motor

PC/-

This is a negative potential terminal in the internal DC main circuit.

PO, PA/+

Terminals for connecting a DC reactor (DCL: optional external device).
Shorted when shipped from the factory. Before installing DCL remove the short
bar.
1-phase 100V models cannot be used with DC reactors. 1-phase 200V models
for Europe are not provided with PO terminal.