Before making a service call

– Trip information and remedies

13.1

Trip causes/warnings and remedies

When a problem arises, diagnose it in accordance with the following table. If it is found that
replacement of parts is required or the problem cannot be solved by any remedy described in the
table, contact your Toshiba dealer.

[Trip information: FL relay activated]

Error
code

Alarm

code

Problem

Possible causes

Remedies

QE

QER

0001

0025

Overcurrent during
acceleration
Overcurrent flowing
in element during
acceleration

• The acceleration time CEE is

too short.

• The V/F setting is improper.
• A restart signal is input to the

rotating motor after a
momentary stop, etc.

• A special motor (e.g. motor with

a small impedance) is used.

• Increase the acceleration time

CEE

.

• Check the V/F parameter.
• Use H (auto-restart) and

H

(ride-through control).

• Increase or decrease the carrier

frequency H.

QE

QER

0002

0026

Overcurrent during
deceleration
Overcurrent flowing
in element during
acceleration

• The deceleration time FGE is

too short.

• Increase the deceleration time

FGE

.

QE

QER

0003

0027

Overcurrent during
operation
Overcurrent flowing
in element during
acceleration

• The load fluctuates abruptly.
• The load is in an abnormal

condition.

• Reduce the load fluctuation.
• Check the load (operated

machine).

QEC

0005

Arm overcurrent at
start-up

• A main circuit element is

defective.

• Make a service call.

QEN

0004

Overcurrent (An
overcurrent on the
load side at start-up)

• The insulation of the output

main circuit or motor is
defective.

• The motor has too small

impedance.

• Check the cables and wires for

defective insulation.

QR

000A

Overvoltage during
acceleration

• The input voltage fluctuates

abnormally.

The power supply has a
capacity of 200kVA or more.

A power factor improvement
capacitor is opened or closed.

A system using a thyrister is
connected to the same power
distribution line.

• A restart signal is input to the

rotating motor after a
momentary stop, etc.

• Insert a suitable input reactor.

• Use H (auto-restart) and

H

(ride-through control).

(Continued overleaf)