Peripheral devices, Danger, 1 selection of wiring materials and devices – Toshiba VF-nC1 User Manual

Page 110

Advertising
background image

E6581090

J-1

10

10. Peripheral devices

  

Danger

Mandatory

• When using wiring materials and their optional devices for the inverter, they must

be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious
injury.

Be Grounded

• Connect earth cables securely. Failure to do so can lead to risk of electric shock

or fire in case of a failure, short-circuit or leak current.

10.1

Selection of wiring materials and devices

Wire size

Voltage

class

Capacity of

applicable

motor

(kW)

Inverter model

Main circuit

(See Note 1.)

DC reactor

(optional)

Grounding cable

0.1

VFNC1S-1001P

AWG 14 / 2.0 mm

2

-

AWG 12 / 3.5 mm

2

0.2

VFNC1S-1002P

AWG 14 / 2.0 mm

2

-

AWG 12 / 3.5 mm

2

0.4

VFNC1S-1004P

AWG 14 / 2.0 mm

2

-

AWG 12 / 3.5 mm

2

Single-

phase

100V
class

0.75

VFNC1S-1007P

AWG 14 / 3.5 mm

2

-

AWG 12 / 3.5 mm

2

0.2

VFNC1S-2002P(L)

AWG 14 / 2.0 mm

2

AWG 16 / 1.25 mm

2

AWG 12 / 3.5 mm

2

0.4

VFNC1S-2004P(L)

AWG 14 / 2.0 mm

2

AWG 16 / 1.25 mm

2

AWG 12 / 3.5 mm

2

0.75

VFNC1S-2007P(L)

AWG 14 / 2.0 mm

2

AWG 14 / 2.0 mm

2

AWG 12 / 3.5 mm

2

1.5

VFNC1S-2015P(L)

AWG 10 / 3.5 mm

2

AWG 14 / 2.0 mm

2

AWG 12 / 3.5 mm

2

Single-

phase

200V
class

2.2

VFNC1S-2022P(L)

AWG 10 / 5.5 mm

2

AWG 14 / 2.0 mm

2

AWG 10 / 5.5 mm

2

0.1

VFNC1-2001P

AWG 14 / 2.0 mm

2

AWG 16 / 1.25 mm

2

AWG 12 / 3.5 mm

2

0.2

VFNC1-2002P

AWG 14 / 2.0 mm

2

AWG 16 / 1.25 mm

2

AWG 12 / 3.5 mm

2

0.4

VFNC1-2004P

AWG 14 / 2.0 mm

2

AWG 16 / 1.25 mm

2

AWG 12 / 3.5 mm

2

0.75

VFNC1-2007P

AWG 14 / 2.0 mm

2

AWG 14 / 2.0 mm

2

AWG 12 / 3.5 mm

2

1.5

VFNC1-2015P

AWG 10 / 2.0 mm

2

AWG 14 / 2.0 mm

2

AWG 12 / 3.5 mm

2

Three-

phase

200V
class

2.2

VFNC1-2022P

AWG 10 / 2.0 mm

2

AWG 14 / 2.0 mm

2

AWG 12 / 3.5 mm

2

Note 1: Sizes of the wires connected to the input terminals R, S and T and the output terminals U, V and W

when the length of each wire does not exceed 30m.

Note 2: For the control circuit, use shielded wires 0.75 mm

2

or more in diameter.

Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: When using a crimp terminal, cover its caulked part with a tube or use an insulated terminal.