Toshiba VF-nC1 User Manual

Page 118

Advertising
background image

E6581090

K-6

11

 

Acceleration/deceleration time parameters

Title

Communication

No.

Function

Unit

Minimum setting

unit Panel/

Communication

Adjustment range

Default

setting

User

setting

Reference

H

0500

Acceleration time 2

s

0.1/0.1

0.1-3000

10.0

6.13

H

0501

Deceleration time 2

s

0.1/0.1

0.1-3000

10.0

6.13

H

0505

Acceleration/decelerat
ion 1 and 2 switching
frequency

Hz

0.1/0.01

0-WN

0.0

6.13

 

Protection parameters

Title

Communication

No.

Function

Unit

Minimum setting

unit Panel/

Communication

Adjustment range

Default

setting

User

setting

Reference

H

0601

Stall prevention level

%

1/1

30-199 (%)
200 (disabled)

150

6.14.1

H

0602

Inverter trip retention
selection

-

-

0: Not retained,
1: Retained

0

6.14.2

H

0603

External input trip stop
mode selection

-

-

0:Coast stop
1:Slowdown stop
2:Emergency DC

braking

0

6.14.3

H

0605

Output phase failure
detection mode
selection

-

-

0:Disabled
1:Selected (Output

open-phase is
checked when
operation is started
for the first time after
power is turned on.)

2:Selected (Output

open-phase is
checked each time
operation is started.)

0

6.14.4

H

0607

Motor 150%-overload
time limit

s

1/1

10~800

300

6.14.5

H

0608

Input phase failure
detection mode
selection

-

-

0: Disabled,
1: Enabled

1

6.14.6

H

0616

Over-torque alarm
level

%

1

0-200

150

6.14.7

H

0618

Over-torque detection
time

s

0.1

0.0-10.0

0.5

6.14.7

H

0627

Under voltage trip
selection

-

-

0:Disabled
1:Enabled (64% or

less: Trip, FL relay
activated)

2:Disabled (50% or

less: Trip, FL relay
not activated)

0

6.14.8

H

0633

Analog input
disconnection
detection

%

1

0 (Disabled), 1 - 100%

0

6.14.9

Advertising