6.14.2 Inverter trip retention

H : Inverter trip retention selection

Function

This parameter is used to prevent the tripped inverter from being restored to working order
when the power is turned back on. The inverter can be restored by resetting it from the
operation panel (terminal).

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Inverter trip retention selection

0: Not retained
1: Retained

0

Up to four sets of latest trip information displayed by the status monitor function can be stored

in memory.

When the power is turned back on, trip information (such as trip current and voltage) stored by

the status monitor function will be cleared.

Error information cleared

Normal operation

Power turned back on:

Error message

displayed

FL not activated

Inverter trips again:

Error message

displayed

FL activated

If the cause of the error or other defective

conditions is not eliminated

Inverter trips.

Panel (terminal) reset

Power reset

6.14.3 External input trip stop

H : External input trip stop mode selection
H : DC braking time (s)

Function

These parameters allow you to specify a method for stopping the inverter when it receives an
external trip stop signal via input terminals or an emergency stop signal from the operation
panel. When the inverter shuts down, the error message “G” is displayed on the inverter’s
display panel and the error FL relay (trip output) is activated. When H is set to 
(emergency DC braking), DC braking time also needs to be set using H.

1) External trip stop by means of a terminal

External trip stop can be performed by means of the a-terminal. Perform the following steps to
assign the external stop function to a terminal and to specify a stopping method.

CC

Input terminal

a-terminal

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

External input trip stop mode
selection

0: Coast stop
1: Slowdown stop
2: Emergency braking stop

0

H

DC braking starting frequency
(Hz)

0.0:OFF
0.1~HJ(Hz)

0.0

H

DC braking current (%)

0~100(%)

50

H

DC braking time (s)

0.0:OFF
0.1~20.0(sec)

1.0