Table of output terminal functions 1

Function

No.

Code

Function

Action

0

LL

Frequency lower limit

ON : Output frequency higher than NN setting

OFF : Output frequency equal to or lower than NN

setting

1

LLN

Inversion of frequency lower limit Inverse output of LL

2

UL

Frequency upper limit

ON : Output frequency equal to or higher than WN

setting

OFF : Output frequency lower than WN setting

3

ULN

Inversion of frequency upper limit Inverse output of UL

4

LOW

Low-speed detection signal

ON : Output frequency equal to or higher than

H

setting

OFF : Output frequency lower than H setting

5

LOWN

Inversion of low-speed detection

signal

Inverse output of LOW

6

RCH

Designated frequency reach

signal (completion of

acceleration/deceleration)

ON : Output frequency within command frequency

±2.5Hz

OFF : Output frequency exceeding command

frequency

±2.5Hz

7

RCHN

Inversion of designated

frequency reach signal (inversion

of completion of

acceleration/deceleration)

Inverse output of RCH

8

RCHF

Set frequency reach signal

ON : Output frequency within H setting

±2.5Hz

OFF : Output frequency exceeding H setting

±2.5Hz

9

RCHFN Inversion of set frequency reach

signal

Inverse output of RCHF

10

FL

Failure FL (trip output)

ON : Inverter trips

11

FLN

Inversion of failure FL (inversion

of trip output)

Inverse output of FL

12

OT

Over-torque detection

ON : Torque current is held above the torque set with

H

for a period of time longer than that set

with H.

13

OTN

Inversion of over-torque

detection

Inverse output of OT