Frequency parameters

Title

Communication

No.

Function

Unit

Minimum setting

unit Panel/

Communication

Adjustment range

Default

setting

User

setting

Reference

H

0201

VI/S3 reference point 1
setting

%

1/1

0-100

0

6.4.1

H

0202

VI/S3 point 1
frequency

Hz

0.1/0.01

0-200

0.0

6.4.1

H

0203

VI/S3 reference point 2
setting

%

1/1

0-100

100

6.4.1

H

0204

VI/S3 point 2
frequency

Hz

0.1/0.01

0-200

*2

6.4.1

H

0240

Starting frequency
setting

Hz

0.1/0.01

0.5-10.0

0.5

6.5.1

H

0241

Operation starting
frequency

Hz

0.1/0.01

0.0-HJ

0.0

6.5.2

H

0242

Operation starting
frequency hysteresis

Hz

0.1/0.01

0.0-HJ

0.0

6.5.2

H

0250

DC braking starting
frequency

Hz

0.1/0.01

0.0-HJ

0.0

6.6.1

H

0251

DC braking current

%

1/1

0-100

50

6.6.1

H

0252

DC braking time

S

0.1/0.1

0.0-20.0

1.0

6.6.1

H

0270

Jump frequency

Hz

0.1/0.01

NN

-WN

0.0

6.7

H

0271

Jumping width

Hz

0.1/0.01

0.0-30.0

0.0

6.7

H

0287

Preset speed operation
frequencies 8

Hz

0.1/0.01

NN

-WN

0.0

H

0288

Preset speed operation
frequencies 9

Hz

0.1/0.01

NN

-WN

0.0

H

0289

Preset speed operation
frequencies 10

Hz

0.1/0.01

NN

-WN

0.0

H

0290

Preset speed operation
frequencies 11

Hz

0.1/0.01

NN

-WN

0.0

H

0291

Preset speed operation
frequencies 12

Hz

0.1/0.01

NN

-WN

0.0

H

0292

Preset speed operation
frequencies 13

Hz

0.1/0.01

NN

-WN

0.0

H

0293

Preset speed operation
frequencies 14

Hz

0.1/0.01

NN

-WN

0.0

H

0294

Preset speed operation
frequencies 15

Hz

0.1/0.01

NN

-WN

0.0

5.11

*2: The value is changed according to the set-up parameter condition.

(VFNC1 (S)-□□□□P□-W type)
FH:80, UL80, VL:60, F127:0, F170:60, F171:200, F204:80, F409:200, F417:1710 for VFNC1 (S)-□□□