Toshiba VF-nC1 User Manual

Page 67

Advertising
background image

E6581090

F-3

6

Function

This parameter is used to switch the function of the VI/S3 terminal between analog signal input
and contact signal input.

Function

This parameter allows you to select a function you want to keep always active (ON). (Only one
function can be selected.)

Specified frequency reach signal: 8
FM/OUT terminal (H)

FL terminal (H)

Output frequency [Hz]

Time [sec]

H

- 2.5Hz

ON
OFF

H

+ 2.5Hz

H

ON
OFF

0

Specified frequency reach reverse signal: 9

FM/OUT terminal (H)
FL terminal (H)
* FM/OUT terminal function selection (HOUN) : 0 (Output frequency)

Note: Activate H to output signals to the FM/OUT terminal, or set H to 8 or 9 to output

signals to the FLA, FLC and FLB terminals.

6.2

Parameters related to terminal function selection

6.2.1 Changing the function of the VI/S3 terminal

H : Analog input/logic input function selection

Parameter setting

Title

Function

Adjustment range

Default setting

H

Analog input/logic
input function
selection

0: Voltage signal, 1: Current signal,
2: Contact input

0

* To use the VI/S3 terminal as a contact input terminal in sink connection, be sure to insert an

adequate resistor* between P15 and VI/S3. (* Recommended resistance: 4.7 k

Ω-1/4W)

6.2.2 Keeping an input terminal function always active

H : Always active function selection (ST)

Parameter setting

Title

Function

Adjustment range

Default setting

H

Always active function
selection (ST)

0~40, 49, 54~57 (See Section 11.)

1 (ST)

6.2.3 Changing the function of an input terminal

H : Input terminal selection 1 (F)
H : Input terminal selection 2 (R)
H : Input terminal selection 3 (S1)
H : Input terminal selection 4 (S2)

H : Analog input/logic input function selection *1
H : Input terminal selection 5 (VI/S3)