How to install

  

Danger

Prohibited

• Do not install and operate the inverter if it is damaged or any component is missing.

This can result in electric shock or fire. Please consult your local agency for
repairs.

Mandatory

• Must be installed in nonflammables such as metals.

The rear panel gets very hot so that if installation is in an inflammable object, this
can result in fire.

• Do not operate with the front panel cover removed. This can result in electric

shock.

• An emergency stop device must be installed that fits with system specifications

(e.g. cuts off input power then engages mechanical brakes).
Operation cannot be stopped immediately by the inverter alone, thus risking an
accident or injury.

• All options used must be those specified by Toshiba. The use of any other option

may result in an accident.

  

Warning

Mandatory

• The main unit must be installed on a base that can bear the unit's weight.

If the unit is installed on a base that cannot withstand that weight, the unit may fall
resulting in injury.

• If braking is necessary (to hold motor shaft), install a mechanical brake. The brake

on the inverter will not function as a mechanical hold, and if used for that purpose,
injury may result.

Installation location

Select a location with good indoor ventilation, place lengthwise in the vertical direction and attach
to a metal wall surface.
If you are installing more than one inverter, the separation between inverters should be at least 5
centimeters, and they should be arranged in horizontal rows.
If the inverters are horizontally arranged with no space between them (side-by-side installation),
peel of the ventilation seals on top of the inverters and operate at 40

°C or less.

Standard installation

Horizontal installation (side-by-side installation)

5 cm or more

5 cm or more

10 cm or more

10 cm or more

10 cm or more

Peel of the ventilation
seals on top of the inverter

Ambient temperature
of 40

°C or less

VFnC1

VFnC1

VFnC1

VFnC1

The space shown in the diagram is the minimum allowable space. Because air cooled equipment
has cooling fans built in on the top or bottom surfaces, make the space on top and bottom as large
as possible to allow for air passage.

Note: Do not install in any location where there is high humidity or high temperatures and where

there are large amounts of dust, metallic fragments and oilmist. If you are going to install
the equipment in any area that presents a potential problem, please consult with Toshiba
before doing so.