Toshiba VF-nC1 User Manual

Page 56

Advertising
background image

E6581090

E-4

5

5.3

Standard default setting

V[R : Standard setting mode selection

Title

Function

Adjustment range

Default setting

V[R

Standard setting
mode selection

0 : -
1 : Default setting 50Hz
2 : Default setting 60Hz
3 : Default setting
4 : Trip clear
5 : Cumulative operation time clear

0

This function will be displayed as 0 during reading on the right. This previous setting is
displayed on the left.
Ex. 3  0

★V[R

cannot be set during the inverter operating. Always stop the inverter first and then program.

[Setting values]

 

50Hz standard setting (V[R=)

To set the following parameters for a base frequency of 50Hz, set the V[R parameter to 1.
(This setting does not affect the settings of any other parameters.)

• Maximum frequency HJ

: 50Hz

• Base frequency 1 XN

: 50Hz

• Base frequency 2 H

: 50Hz

• Upper limit frequency WN : 50Hz

• VI/S3 point 2 frequency H : 50Hz

• Motor rated speed H : 1410min

-1

 

60Hz standard setting (V[R=)

To set the following parameters for a base frequency of 60Hz, set the V[R parameter to 2.
(This setting does not affect the settings of any other parameters.)

• Maximum frequency HJ

: 60Hz

• Base frequency 1 XN

: 60Hz

• Base frequency 2 H

: 60Hz

• Upper limit frequency WN : 60Hz

• VI/S3 point 2 frequency H : 60Hz

• Motor rated speed H : 1710min

-1

 

Default setting (V[R=)

Setting V[R to  will return all parameters to the standard values that were programmed at the

factory.

When 3 is programmed, < KPKV will be displayed for a short time after setting and will then

be erased and displayed the original indication “PQ” (Setup parameter). (Only for VFNC1 (S)-
□□□□

P□-W type) This setting clears all trip history data but it does not clear cumulative

operation time data. This setting does not affect the settings of the following parameters.

• FM/OUT terminal functions selection HOUN

• Meter adjustment HO

• Analog input/logic input function selection H • Sink/source selection H
• Free notes H

See 4.1.1 for setting of setup parameters.

 

Trip clear (V[R=)

Setting V[R to  initializes the past four sets of recorded error history data.

* (The parameter does not change.)

 

Cumulative operation time clear (V[R=)

Setting V[R to  allows the initial resetting of the cumulative operation time monitor (0 [zero]
time).

* (The parameter does not change.)

Function

Allows setting of all parameters to the standard default setting, etc. at one time. (Except

the setting of HO)