E6581090

E-12

5

SS3 (preset speed 3) and SS4 (preset speed 4) are not assigned to any terminals at the factory.
Before use, therefore, assign SS3 and SS4 to reserved terminals, using the input terminal
function selection parameter. In the above example, these functions are assigned to the R and
VI/S3 terminals.

[Example of a connection diagram] (When the input terminals are placed in sink logic mode)

F (Forward run)

CC

S2

R

S1

Forward

Preset speed 1

Preset speed 4

Preset speed 3

Preset speed 2

P15

VI/S3

*1 : When using the VI/S3 terminal as a contact input terminal, be sure to insert a resistor* between

the P15 and VI/S3 terminals. (* Recommended resistance: 4.7k

Ω-1/4W)

3) Using other speed commands with preset speed command

Command mode

selection

EOQF

: Terminal board

1 : Operation panel

Frequency

setting mode

selection

HOQF

: Terminal

board

(Analog signal)

1 : Operation

panel

2 : Potentiometer

: Terminal

board

(Analog signal)

1 : Operation

panel

2 : Potentiometer

Entered

Preset speed command Valid Note)

Preset

speed

command

Not

entered

Analog signal

Valid

Operation

panel

Command

Valid

Potentiometer

Valid

Analog signal

Valid

Operation

panel

Command

Valid

Potentiometer

Valid

Note) The preset speed command is always given priority when other speed commands are input at

the same time.

Below is an example of 3-step speed operation with standard default setting.

F-CC

S1(SS1)-CC

S2(SS2)-CC

ON
OFF

ON
OFF

ON
OFF

UT

UT

UT

Output frequency
[Hz]

Time
[s]

0

Example of 3-step speed operation

*1

(The inverter doesn’t accept preset speed command.)