E6581090

F-10

6

6.5

Operation frequency

6.5.1 Starting frequency

H : Starting frequency setting (Hz)

Function

The frequency set with the H parameter is put out immediately after the completion of
frequency setting.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Starting frequency setting (Hz) 0.5~10.0(Hz)

0.5

Starting frequency setting

H

Output frequency [Hz]

Time [sec]

0

6.5.2 Start/stop control by means of frequency setting signals

H : Operation starting frequency (Hz)
H : Operation starting frequency hysteresis (Hz)

Function

The start/stop of operation can be controlled, by simply using frequency setting signals.

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Operation starting frequency
(Hz)

0.0~HJ (Hz)

0.0

H

Operation starting frequency
hysteresis (Hz)

0.0~HJ (Hz)

0.0

0

A

B

100%  Frequency command value

H + H

H

H - H

HJ

The inverter starts to accelerate when the

frequency setting signal reaches point B.
Deceleration starts when the frequency

setting signal falls below point A.

Output frequency [Hz]