Toshiba VF-nC1 User Manual

Page 90

Advertising
background image

E6581090

F-26

6

6.14.9 Analog input disconnection detection

H : Analog input disconnection detection

Function

This parameter is used to detect a break in an analog signal to the VI/S3 terminal. If an analog
signal is below the level set with H for 0.3 seconds (approx.), the inverter will assume the
signal to be broken and it will trip and display the error message “G.” (The Analog input
disconnection detection function is disabled if H is set to 0.0%.)

Title

Function

Adjustment range

Default setting

H

Analog input
disconnection detection

0: Disabled
1~100%

0

6.15

Operation panel parameters

6.15.1 Prohibiting the change of parameter settings

H : Prohibition of change of parameter settings

Function

This parameter specifies whether parameter setting is changeable or not.

Setting methods

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Prohibition of

change parameter

settings

0~7 (See the explanation below.)



: Permitted _____ EOQF and HOQF settings cannot be changed during operation. (Default)



: Prohibited _____ All parameters are read/write-protected.



: Permitted _____ EOQF and HOQF settings also can be changed during operation.



: Prohibited _____ Frequency can be changed from the operation panel but all other

parameters are read/write-protected.



: Permitted _____ The emergency stop function cannot be controlled from the operation panel

and EOQF and HOQF settings cannot be changed during operation.



: Prohibited _____ The emergency stop function cannot be controlled from the operation panel

but all parameters are read/write-protected.



: Permitted _____ The emergency stop function cannot be controlled from the operation panel

and EOQF and HOQF settings also can be changed during operation.



: Prohibited _____ The emergency stop function cannot be controlled from the operation panel,

frequency can be changed on the operation panel, but any other parameters
are write/read-protected.

Note: Some parameters cannot be changed during operation, no matter how H is set. (See

4.1.4.)

Canceling the setting
Only the setting of H can be changed anytime, no matter how it is set.