• Operate in areas where ambient temperature ranges from -10°C to 50°C. However, when

installing the inverter where the ambient temperature will rise above 40°C, detach the caution
label on the top surface.

5cm

5cm

5cm

Measurement
position

Measurement
position

Note: The inverter is a heat-emitting body. Make sure to provide proper space and ventilation

when installing in the cabinet. When installing the inverter in a cabinet, you are
recommended to detach the caution label even if the temperature in the cabinet is below
40°C.

• Do not install in any location that is subject to large amounts of vibration.

• If the VF-nC1 Inverter is installed near any of the equipment listed below, provide measures to

insure against errors in operation.

Solenoids:

Attach surge suppressor on coil.

Brakes:

Attach surge suppressor on coil.

Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights:

Attach surge suppressor on coil.

Resistors:

Place far away from VF-nC1
Inverter.